ReSound UP977-DLW Especificações

Consulte online ou descarregue Especificações para Geradores de energia ReSound UP977-DLW. ReSound UP977-DLW Specifications Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 26
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 0
SECTION VIII
(Sub-Section 472)
Diesel Engine Driven Generator With
Weatherproof Enclosure
Article Page
1. General 472-1 thru 472-8
2. Products 472-8 thru 472-23
3. Execution 472-23 thru 472-25
4. Measurement and Payment 472-25
Vista de página 0
1 2 3 4 5 6 ... 25 26

Resumo do Conteúdo

Página 1

SECTION VIII (Sub-Section 472) Diesel Engine Driven Generator With Weatherproof Enclosure Article Page 1. General 472-1

Página 2

2.2.2 The engine shall be capable of satisfactory performance on No. 2 fuel oil (ASTM Designation D396). Diesel engines requiring a premium

Página 3

2.2.8 The engine shall be provided with removable wet-type cylinder liners of close grained alloy iron, heat treated for proper hardness as

Página 4

2.3.3 Provide one (1) or two (2) unit mounted thermal circulation type water heaters incorporating a thermostatic switch shall be furnished

Página 5

2.4.3.3 Generator stator and exciter stator windings shall be a full Class H insulated system vacuum impregnated with epoxy resin which aft

Página 6

2.4.5.1 Voltage Regulator: 2.4.5.1.1 The generator MANUFACTURER shall furnish a hermetically sealed, silicon controlled rectifier type volta

Página 7

2.6 WEATHER-PROTECTIVE ENCLOSURE 2.6.1 The intent of this Specification is to provide a weatherproof type generator set enclosure complet

Página 8

2.6.2.4 Components – All component s of the enclosure shall be assembled utilizing 0.375-inch minimum stainless steel bolts, nuts, and lock wash

Página 9

2.6.2.9.1 Rain dress for exhaust pipe and tail pipe extension. Rain dress shall prevent the entrance of rain and allow the expansio

Página 10

2.7.4 Base Tank – The unit shall be equipped with a double wall in-base fuel tank and shall be supplied with a lockable, exterior located fill cap.

Página 11

2.9 AUTOMATIC STARTING SYSTEM 2.9.1 Starting Motor – A DC electric starting system with positive engagement shall be furnished for th

Página 12

DIESEL ENGINE DRIVEN GENERATOR WITH WEATHERPROOF ENCLOSURE SUB-SECTION 472 1.0 GENERAL 1.1 SCOPE OF WORK 1.1.1 Furnish all labor, materials, eq

Página 13

2.10 MAIN LINE CIRCUIT BREAKER 2.10.1 Type – Main line, molded case circuit breaker mounted upon and sized to the output of the generator sha

Página 14

2.11.1.5 Automatic starting controls as previously specified. 2.11.1.6 Voltage level adjustment rheostat with locking knob 2.11.1.7 Dry conta

Página 15

2.11.4 Timing Functions – All control panel timing functions shall be accomplished by metal encased, solid-state, plug-in timing relay

Página 16

2.12.4 The transfer switch shall be listed under U.L. 1008, in NEMA 1 enclosure, as manufactured by Lexington Switch and Controls, Inc., Le

Página 17

2.12.5.11 Engine starting contacts to provide for generator starting from each unit independent of the other. 2.12.5.12 One (1) auxiliary

Página 18

3.2 PAINTING 3.2.1 The engine generator set and associated equipment shall be shop primed and finish coated in accordance with the Manufact

Página 19

3.5 WARRANTY 3.5.1 Equipment furnished under this Section shall be guaranteed against defective parts and workmanship under terms of

Página 20

1.3 QUALIFICATIONS 1.3.1 The engine-generator set shall be the standard product, as modified by these specifications, of a MANUFACTURER reg

Página 21

1.3.6 All materials and parts comprising the unit shall be new and unused, of current manufacture, and of the highest grade, free from all

Página 22

1.4.4.2 Engine Data: A. MANUFACTURER B. MODEL C. Number of Cylinders D. RPM E. Bore x stroke F. BMEP at full rated load G. Piston speed, FPM

Página 23

1.4.4.4.2 Legends for all devices on all diagrams. 1.4.4.4.3 Sequence of operation explanations for all portions of all schematic wiring diagr

Página 24

1.4.11 Submit to the ENGINEER the written warranty as required in Paragraph 3.06 below. 1.5 TESTING: To assure that the equipment has been

Página 25

1.5.2 Final Production Tests: Each generator set shall be tested under varying loads with guards and exhaust system in place. Tests shall i

Página 26

1.6 SPECIAL TOOLS AND SPARE PARTS 1.6.1 Furnish one (1) set of all special tools required for normal operation and maintenance of the equipment

Comentários a estes Manuais

Sem comentários